RefleX 1505
- Overcurrent, Directional EF, Phase-Unbalance and Autoreclosure
relay
|
|
|
|
|
This relay includes a 3-phase Overcurrent module with
2 separate current/timer levels, a Directional EF module with two
current/timer levels and a negative sequence measurement module for
Phase-Unbalance detection.
The common Autoreclosure module can be
programmed freely for 1...6 shots, or completely disabled (not appearing
in the menu). |
The relay is extremely well suited for distribution
power lines in systems with high resistance neutral grounding. In cable
networks the Autoreclosure should be disabled. |
|
|
|
|
|